Treatment
Altitude [m]
Air flow [m³/h]
Inlet T [°C]
Inlet RH [%]
Humidifier
Efficiency [%]
Final T [°C]
Final RH [%]

Air properties at each point

Pointt [°C]φ [%]x [g/kg]h [kJ/kg]v [m³/kg]ρ [kg/m³] T dew [°C]T wet [°C]V [m³/h]dry air [kg/h]moist air [kg/h]
1 Inlet 5.080.04.31 15.90.7931.266 1.83.6 10,00012,60312,658
2 Pre-heating coil outlet 28.917.54.31 40.10.8621.166 1.814.4 10,86012,60312,658
3 Humidifier outlet 16.579.69.30 40.10.8331.212 12.914.3 10,49612,60312,721
4 Final outlet 24.050.09.30 47.80.8541.181 12.917.1 10,76812,60312,721

Powers and water per step heating +, cooling −; sensible = ṁ·(cpa + x·cpv)·ΔT, latent = total − sensible

StepFrom → ToΔT [K]Total [kW]Sensible [kW]Latent [kW]Water [kg/h]
Pre-heatingInlet → Pre-heating coil outlet +23.9+84.96 +84.960.00 0.00
Adiabatic humidificationPre-heating coil outlet → Humidifier outlet -12.40.00 -44.18+44.18 +62.82
Post-heatingHumidifier outlet → Final outlet +7.5+26.92 +26.920.00 0.00